4080

Parameters:

Definitions:

Reactions:


Remedy:


Program Continuation:


Incorrect configuration of indexing axis in MD %1

%1 = String: MD identifier

The assignment of a position table to an indexing axis or the contents of a position table contains an error, or the length of a position table has been parameterized with 0.

-    NC not ready.

-    Mode group not ready, also effective for single axes

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

Please inform the authorized personnel/service department. 3 MD identifiers are output, depending on the type of error.

1.    $MA_INDEX_AX_ASSIGN_TAB (axis-specific MD 30500: The error is due to multiple assignment of a position table (NCK MD 10910/10930 INDEX_AX_POS_TAB_n) to axes with different types (linear/rotary axis).

2.    $MN_INDEX_AX_POS_TAB_n (NCK MD 10910/10930): The contents of the displayed table n contain an error.

The entered positions must be arranged in increasing size.

A particular position must not be set more than once.

If the table is assigned to one or several modulo axes, then the contents must be within the 0 to < 360 degree range.

3.    $MN_INDEX_AX_LENGTH_POS_TAB_n (NCK MD 10900/10920): The length of the displayed position table n was specified with 0.

Clear alarm with the RESET key. Restart part program