18200


Parameters:

Definitions:


Reactions:


Remedy:

Program Continuation:


Channel %1 block %2 curve table: block search stop not allowed with definition CTABDEF

%1 = Channel number %2 = Block number, label

Program instructions that lead to a preprocessing stop are not allowed within a curve table definition. The system variable $P_CTABDEF can be queried to check whether a table definition is currently active.

-    Interpreter stop

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

Put the block in parenthesis using "IF NOT($P_CTABDEF) ... ENDIF" or remove the instruction that causes the preprocessing stop. Then start the part program again. Clear alarm with the RESET key. Restart part program