21703

Parameters:


Definitions:


Reactions:


Remedy:


Program Continuation:


Channel %1 block %3 axis %2 touch probe not deflected, illegal edge polarity

%1 = Channel number

%2 = Axis name, spindle number

%3 = Block number

The selected probe is not (!) deflected and therefore cannot record any measured value from the deflected to the non-deflected state.

Measurement level 2 (MEAWA, MEASA, MEAC)

The degree of deflection of the probe at the start of the measurement task is identical to the first programmed measurement signal edge. The test is only performed in mode 2.

-    Local alarm reaction.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

Check probe

Check start positioning for measuring Check program

Clear alarm with the RESET key. Restart part program


1-1067