27224

PROFIsafe: F module MD %1[%2] - MD %3[%4]: double assignment of PROFIsafe address

Parameters:

%1 = MD name 1 %2 = MD array index 1 %3 = MD name 2

Definitions:

%4 = MD array index 2

In the NCK MD or in the S7 F parameters, the same PROFIsafe address has been parameterized for the F modules parameterized in the specified machine data. Therefore, no clear communication link is possible between F master and F slave.

Reactions:

-    Mode group not ready.

-    Channel not ready.

-    NC Start disable in this channel.

Remedy:

Program Continuation:

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

Check and correct the S7 F parameterization and NCK MD.

Switch control OFF - ON.

© Siemens AG 2005 All Rights Reserved

1-1254