27242

Parameters:

Definitions:


Reactions:


Remedy:


Program Continuation:


PROFIsafe: F module %1, %2 faulty

%1 = PROFIsafe address %2 = Incorrect F parameter

An error was detected during the evaluation of the F parameters.

%2 = CRC1: CRC specified by F parameters faulty.

%2 = F_WD_Timeout: The monitoring time parameterized in Step 7 is too small for the PROFIsafe cycle time defined by the MD $MN_PROFISAFE_IPO_TIME_RATIO.

%2 = CRC2_Len: CRC message length faulty.

%2 = F_Data_Len: the telegram length defined for the specified module is incorrect.

-    Mode group not ready.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

%2 = CRC1: PLC overall reset, reload the S7 F configuration.

%2 = F_WD_Timeout: reparameterize the PROFIsafe cycle time or F monitoring time. %2 = CRC2_Len: PLC overall reset, reload the S7 F configuration.

%2 = F_Data_Len: PLC overall reset, reload the S7 F configuration.

Switch control OFF - ON.