Axis %1 drive %2 fixed link voltage of axes differ
%1 = NC axis number %2 = Drive number
An unequal fixed voltage MD1161: $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage) has been found for axes of a drive module. Since a fixed voltage <> 0 replaces the measured DC link voltage value, but the DC link voltage value is measured only once for all axes of a drive module, the fixed voltage must be identical on all module axes before it is accepted.
The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready).
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Please inform the authorized personnel/service department. Set the same fixed voltage (MD 1161) on all module axes. $MD_FIXED_LINK_VOLTAGE (DC link fixed voltage) has been found for axes of a drive module.
Clear alarm with the RESET key in all channels. Restart part program.