Remedy:
Program Continuation:
Axis %1 drive %2 reactance less than or equal to zero
%1 = NC axis number %2 = Drive number
The value in MD 1139: $MD_STATOR_LEAKAGE_REACTANCE (stator leakage reactance) or MD 1140: $MD_ROTOR_LEAKAGE_REACTANCE (rotor leakage reactance) or MD 1141: $MD_MAGNETIZING_REACTANCE (magnetizing reactance) is less than or equal to zero.
The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready).
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Please inform the authorized personnel/service department.
For standard motors: Reset the drive (delete the bootfile) and repeat the startup.
For third-party motors: Check and, if necessary, refer to the motor data sheet to correct MD 1139: $MD_STATOR_LEAKAGE_REACTANCE (stator leakage reactance) or MD 1140: $MD_ROTOR_LEAKAGE_REACTANCE (rotor leakage reactance) or MD 1141: $MD_MAGNETIZING_REACTANCE (magnetizing reactance).
Clear alarm with the RESET key in all channels. Restart part program.