Reactions:
Remedy:
Program Continuation:
Axis %1 drive %2 bandwidth numerator larger than double blocking frequency
%1 = NC axis number %2 = Drive number
The bandwidth numerator of a speed or manipulated variable setpoint filter is greater than twice the blocking frequency.
This error message is only issued for the general bandstop filter if:
Speed filter 1:
MD 5516 > 0.0 or MD 5520 <> 100.0 Manipulated variable filter 1:
MD 5212 > 0.0 Manipulated variable filter 2:
MD 5215 > 0.0
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
The bandwidth numerator must be less than twice the blocking frequency.
Speed filter 1:
BSP bandwidth numerator drive MD 5516: SPEED_FILTER_1_BW_NUMERATOR BSP blocking frequency drive MD 5514: SPEED_FILTER_1_SUPPR_FREQ, MD 5516 <= 2 * MD 5514 Manipulated variable filter 1:
BSP bandwidth numerator drive MD 5212: OUTPUT_VCTRL_FIL_1_BW_NUM BSP blocking frequency drive MD 5210: OUTPUT_VCTRL_FIL_1_SUP_FREQ, MD 5212 <= 2 * MD 5210 Manipulated variable filter 2:
BSP bandwidth numerator drive MD 5215: OUTPUT_VCTRL_FIL_2_BW_NUM
BSP blocking frequency drive MD 5213: OUTPUT_VCTRL_FIL_2_SUP_FREQ, MD 5215
<= 2 * MD 5213
Clear alarm with the RESET key in all channels. Restart part program.