310771

Parameters:

Definitions:

Reactions:


Remedy:

Program Continuation:


Axis %1 drive %2 gain in fine area of valve characteristic is less than or equal to zero

%1 = NC axis number %2 = Drive number

The gradient in the fine area of the valve characteristic is less than or equal to zero.

-    NC not ready.

-    The NC switches to follow-up mode.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

-    NC Stop on alarm.

-    Channel not ready.

The gradient in the fine area is calculated as follows:

Positive quadrant: (MD 5464 - MD 5480) / (MD 5465 -5481)

Negative quadrant: (MD 5467 - MD 5483) / (MD 5468 - 5484)

Enter a valid combination in the above drive MD.

Clear alarm with the RESET key in all channels. Restart part program.