380003

Parameters:


Definitions:


Reactions:


Remedy:


Program Continuation:


Profibus-DP: operating error, reason %1, parameter %2 %3 %4.

%1 = Cause of the error %2 = Parameter 1 %3 = Parameter 2 %4 = Parameter 3

An operating error occurred on the PROFIBUS DP in cyclic mode.

Overview: Cause of the error, Par 1, Par 2, Par 3:

01 = unknown alarm, alarm class, logical address, -02 = DPM cycle timeout, DPM actual value status, DPM setpoint value status, -03 = DPM cycle status, DPM actual value status, DPM setpoint value status, DPM error code

04    = DPM cycle error, DPM actual value status, DPM setpoint value status, DPM error code

05    = client not registered, client number, max. number of clients, -06 = synchronisation error, number of sync violation, --, -07 = spinlock timeout, PLC spinlock, NCK spinlock

Digit 1000 of the error cause = number of the affected bus Alarm class: (see alarm 380 060)

The following can be primary causes:

For error cause 01: Data transfer error on PROFIBUS DP

For error cause 02, 03, 04: Error in contents of SDB1000

For error cause 02, 03, 04, 05, 07: Corruption of parts of system program

For error cause 06: The PCI bus cycle does not match the expected rate and

synchronization is not possible for this reason. The correct PCI bus cycle must be

entered.

The error can also be caused by a hardware problem on the MCI module.

-    Channel not ready.

-    NC Start disable in this channel.

-    Interface signals are set.

-    Alarm display.

For error cause 01:

Check the electrical and fault-related specifications for PROFIBUS DP, assess the cable installation

Check the terminating resistors of the PROFIBUS connectors (ON setting at end of cable, otherwise OFF setting required)

Check slave

For error cause 02, 03, 04:

Check SDB1000

For error cause 02, 03, 04, 05:

Follow the procedure described for troubleshooting alarm 380 001 For error cause 06:

The correct PCI bus cycle must be entered.

If the error cannot be eliminated by this procedure, please make a note of the error text and contact the control system manufacturer.

Clear alarm with the RESET key. Restart part program


1-2763